a) Formwork – Rigid, true to line and level, removal time as per Table 7.4.4(a). b) Placing – Max free fall 1.5m, no segregation. c) Compaction – Mechanical vibrator, not contacting reinforcement. d) Curing – Minimum 7 days wet hessian or curing compound.

Grade 30 – 1:2:4 mix with maximum water-cement ratio 0.55. Grade 35 – Designed mix with minimum cement content 350 kg/m³. standard specification for building works 2020 jkr pdf

This clause covers the supply, mixing, transporting, placing, compacting, curing and finishing of structural concrete for all reinforced concrete elements excluding pre-cast concrete. a) Formwork – Rigid, true to line and

Slump test – every 50m³. Cube test – 3 cubes per 50m³, tested at 7 & 28 days (MS 26). d) Curing – Minimum 7 days wet hessian or curing compound

a) Cement – Ordinary Portland Cement complying with MS 522: Part 1. b) Coarse aggregate – 20mm nominal size, crushed granite, complying with MS 30. c) Fine aggregate – Natural sand, grading Zone 2, MS 30. d) Water – Clean, free from oils, acids, alkalis, or organic matter.